Add to Cart
1. Product Description
Aerial bundled cables are mainly used for secondary overhead lines on poles or as feeders to residential premises.
Basic design to IEC 60502 / AS/NZS 3599-1 standards
2. Usage
To be used at cotages of 600V phase-to-phase or less and at conductor temperatures not to exceed 75oC for polyethylene insulated conductors or 90oC for crossliked polyethylene(XLPE) insulated conductors.
3. Standards
(1). BS 7870-5: Part 5: Polymeric insulated aerial bundled conductors (ABC) of rated voltage 0.6/1 kV for overhead distribution
ABC Cables without Street Lighting | |||||||
1+1 Structure | |||||||
Phase Conductor | Neutral Conductor | Completed Cable | |||||
Section | Insulation Thickness | Electrical Resistance | Section | Insulation Thickness | Electrical Resistance | Overall Diameter | Cable Weight |
DC.20°C | DC.20°C | ||||||
No.xmm2 | mm | Ω/km | mm2 | mm | Ω/km | mm | kg/km |
1x25 | 1.3 | 1.20 | 25 | 1.3 | 1.20 | 17.6 | 210 |
1x35 | 1.3 | 0.868 | 35 | 1.3 | 0.868 | 19.6 | 270 |
1x50 | 1.5 | 0.641 | 50 | 1.5 | 0.641 | 23 | 360 |
1x70 | 1.5 | 0.443 | 70 | 1.5 | 0.443 | 26.4 | 500 |
1x95 | 1.7 | 0.320 | 95 | 1.7 | 0.320 | 30.6 | 680 |
3+1 Structure | |||||||
Phase Conductor | Neutral Conductor | Completed Cable | |||||
Section | Insulation Thickness | Electrical Resistance | Section | Insulation Thickness | Electrical Resistance | Overall Diameter | Cable Weight |
DC.20°C | DC.20°C | ||||||
No.xmm2 | mm | Ω/km | mm2 | mm | Ω/km | mm | kg/km |
3x25 | 1.3 | 1.20 | 25 | 1.3 | 1.20 | 21.2 | 410 |
3x35 | 1.3 | 0.868 | 35 | 1.3 | 0.868 | 23.7 | 550 |
3x50 | 1.5 | 0.641 | 50 | 1.5 | 0.641 | 27.8 | 730 |
3x70 | 1.5 | 0.443 | 70 | 1.5 | 0.443 | 31.9 | 1000 |
3x95 | 1.7 | 0.320 | 95 | 1.7 | 0.320 | 36.9 | 1370 |
3x120 | 1.7 | 0.253 | 120 | 1.7 | 0.253 | 40.6 | 1690 |
ABC Cables with Street Lighting | |||||||
3+1+1 Structure | |||||||
Phase Conductor | Neutral Conductor | Street Lighting Conductor | Completed Cable | ||||
Section | Insulation Thickness | Section | Insulation Thickness | Section | Insulation Thickness | Overall Diameter | Cable Weight |
No.xmm2 | mm | mm2 | mm | mm2 | mm | mm | kg/km |
3x50 | 1.5 | 50 | 1.5 | 25 | 1.3 | 29.8 | 830 |
3x70 | 1.5 | 70 | 1.5 | 25 | 1.3 | 33.6 | 1100 |
3x95 | 1.7 | 95 | 1.7 | 25 | 1.3 | 38.2 | 1470 |
4. FAQ
(1).Are you a manufacturer or trading company?
We are a leading and profesional manufacturer of cable and wire, including: LV power cable, ABC, bare conductor, building wire, control cable and so on, with high quality.
(2). Is it sample available?
For stock product, of course, the sample is available for free. The sample will be released against the freight, and freight collect is also acceptable.
(3). Can we represent your SANWU CABLE to bid?
Highly welcome! We are looking for agency or partner in your local to promote our products, develop business, accordingly, we will provide nice condictions to make you get rich return.
(4). How about the package?
We can pack our products, by coil, carton, plastic bag, wooden drum/reel, steel-wooden drum/reel, steel drum/reel with strong protection to suit for the long-distance delivery.
5. Available Samples:
6. Factory Cable making machines:
7. Packing&Delivery: